Showing posts with label ball valve. Show all posts
Showing posts with label ball valve. Show all posts

Applying Gas Pipeline Block Station Valves


A block valve is used on gas transmission systems to isolate a segment of the main gas pipeline for inspection and maintenance, or for shutdown in the case of a natural disaster or pipeline damage.

The block valve is typically a full-bore, soft seated ball valve to allow for scraping. However, this type of valve cannot be opened against full differential pressure without damage to the valve seats. Therefore, a bypass system is installed around the block valve, and used to balance the pipeline pressure prior to opening. Plug valves should be used in the bypass as they are capable of opening and throttling against full differential pressure without damage.

The Requirement of a Bypass

Let's see what would happen if the block valve, which is a soft seated ball valve, was operated against full differential pressure. As it is initially opened the huge pressure drop across the valve generates high velocity flow carrying fine dust, rust, or scale particles in close proximity of the valve seats. This results in seat damage and a block valve that cannot seal bubble tight once closed.

The Bypass Valve Sequence

To avoid this, a bypass system is utilized to balance the pressure either side of the block valve prior to opening it. With the vent valve closed, bypass valve 1 is opened allowing pressure into the bypass. In this case, a plug valve should be used, as it can be opened against full differential pressure without seat damage. Now bypass valve 2 is slowly opened, gradually building pressure in the downstream section until the pressure either side of the block valve is equalized. A plug valve is also used here capable of throttling the flow without seat damaged. With the pressure now equalized the block valve can be opened safely without the risk of seat damage. The two bypass valves have now done their job and can be closed providing bubble tight shutoff against the main pipeline.

Venting a Pipeline Section

Block stations are also used to vent sections of the pipeline into the atmosphere. This operation would start with all valves in the closed position. Bypass valve 1 is then opened allowing pressure into the bypass station. The vent valve is now slowly opened to release the pipeline pressure. Once again, this is a demanding application opening against full differential pressure, hence a plug valve is used to ensure bubble tight isolation to the atmosphere once closed.

For more information, contact Swanson Flo by visiting https://swansonflow.com or by calling 800-288-7926.

Worcester Controls Valve and Actuator Product Catalog

Here is a new Product Catalog for Flowserve Worcester Control industrial ball valves, pneumatic actuators and electric actuators, courtesy of Swanson Flo.  These include standard flanged ball valves, ANSI and DIN specifications in reduced and full bore, three-piece valves for cryogenic, high pressure, steam, diverter or sampling duty, high integrity valves, multi-way designs, modulating controls or customized solutions.

DelVal Flow Control - Ball Valves, Butterfly Valves, Actuators

DelVal Flow Control offers high quality butterfly valves, ball valves, and quarter turn actuators that provide smooth, controlled and dependable flow of fluids through pipelines in process plants.

Products Include:  
  • Resilient seated butterfly valves 
  • Lined butterfly valves 
  • High-performance butterfly valves (double and triple offset) 
  • Trunnion mounted ball valves 
  • Floating ball valves
  • Actuators
800-288-7926